We offer the most competitive prices for HVAC Heating Cooling Air Conditioning products and installation in Arlington – Alexandria – Northern Virginia – Washington DC and Maryland
DCM601A71 Intelligent Touch Manager Control System
Call Perry Aire today 703-521-2226!
Offering DCM601A71 Intelligent Touch Manager Control Systems in:
VIRGINIA: Arlington, Alexandria, Annandale, Arlington, Ashburn, Burke, Centreville, Chantilly, Crystal City, Dale City, Dulles, Fairfax, Falls Church, Fort Belvoir, Great Falls, Herndon, Leesburg, Lincoln, Lorton, Manassas, McLean, Oakton, Purcellville, Reston, Springfield, Stafford, Sterling, Vienna, Woodbridge.
MARYLAND: Annapolis, Aspen Hill, Beltsville, Bethesda, Chevy Chase, College Park, Gaithersburg, Hampstead, Hyattsville, Lanham, Laurel, Montgomery Village, Potomac, Rockville, Silver Spring, Takoma Park, Temple Hills, National Harbor, Cabin John, East Riverdale, Riverdale, Landover, Cheverly, Oxon Hill, Fort Washington, Indian head, Morningside.
WASHINGTON, DC
DCM601A71 Intelligent Touch Manager Control System
The Touch Manager (version 1.02) is Daikin’s intelligent AC controller and provides control for all VRV, SkyAir, and Daikin RA and FTXS indoor units with the use of the KRP928BB2S RA Adapter. This HVAC controller is capable of controlling a maximum of 64 indoor unit groups and 128 indoor units connected to a maximum of 10 outdoor units.
- The intelligent Touch Manger has a backlit 10.4″ LCD display.
- Information can be displayed in one of nine languages
- Area and Group configuration
Features
Support weekly schedule settings.
7 day weekly pattern
100 independent schedules configurable with up to 20 events for each days schedule
Each scheduled event includes On/Off, Operation Mode, Occupied Setpoint, Pre-Cool, Pre-Heat, Setback High, Setback Low, Remote Controller On/Off Prohibit, Remote Controller Mode Prohibit, Remote Controller Setpoint Prohibit, Timer Extension Setting, Fan Speed, and Setpoint Range Limit
Relative Setback setpoints for Cool and Heat when unit is Off (unoccupied)
Timer Extension used for a timed override (settable from 30 – 180 minutes) to allow indoor unit operation during the unoccupied period
A maximum of 40 exception days can be scheduled on the yearly schedule (repeats yearly)
Exception days will be used to override specified days on the weekly schedule based upon irregular occupied/unoccupied conditions
Exception days can be configured on a set date (Jan 1) or floating date (1st Monday in September)
Auto-changeover provides Fixed, Operating, and Averaging changeover methods for both Heat Pump and Heat Recovery systems based upon the changeover group configuration. This will allow for the optimal room temperature to be maintained by automatically switching the indoor unit’s mode between Cool and Heat in accordance with the room temperature and setpoint